Lithium-ion batteries charged to full capacity were far more likely to catch fire or undergo thermal runaway when subjected to external pressure, according to tests released by Seoul on Monday, raising questions about safety practices in warehouses storing large quantities of batteries. The Seoul Metropolitan Fire and Disaster Headquarters said four out of five batteries in both cylindrical and pouch-shaped categories experienced thermal runaway and ignition when charged to 100 percent. The tests were conducted by the headquarters’ Fire Investigation Research Center following a July fire at a logistics center in Incheon, as authorities examined whether battery charge levels should be regulated during distribution and storage. Researchers tested two commercially available types — cylindrical 18650 lithium-ion batteries and pouch-shaped lithium-ion polymer batteries — at charge levels of 30 percent, 50 percent, 70 percent and 100 percent. Five tests were conducted at each charge level, with researchers applying controlled external pressure using a pneumatic press and monitoring volta